CaCO3
JACAN

How to check and maintain the instruments (pressure gauges, thermocouples)

Reading time:
minutes

This guide is site-practical for graphite grinding/milling/purification systems, focusing on anti-dust, anti-condensation, explosion-proof requirements, and stable readings for grinding pressure, air pressure, temperature, and differential pressure. General Safety & Pre-Requisites (Must Follow First) Lockout / Tagout (LOTO)Isolate power, air supply, and nitrogen purge before disassembling any instrument; no live/depressurized operation. Graphite Dust SafetyWear P100 respirator, anti-static coveralls, conductive gloves; no iron knocking, friction sparks. Environment ControlKeep instrument room/box humidity 40%–55% to avoid condensation; clean graphite dust regularly. Explosion-Proof ComplianceAll instruments in grinding zones must be Ex d IIC T4 ATEX-certified; keep grounding resistance ≤4Ω. 1. Pressure Gauges & Pressure Transmitters Inspection & Maintenance Covers: ordinary pressure gauges, digital pressure transmitters, differential pressure (DP) meters for mill air pressure, bag filter…

This guide is site-practical for graphite grinding/milling/purification systems, focusing on anti-dust, anti-condensation, explosion-proof requirements, and stable readings for grinding pressure, air pressure, temperature, and differential pressure.

General Safety & Pre-Requisites (Must Follow First)

  1. Lockout / Tagout (LOTO)Isolate power, air supply, and nitrogen purge before disassembling any instrument; no live/depressurized operation.
  2. Graphite Dust SafetyWear P100 respirator, anti-static coveralls, conductive gloves; no iron knocking, friction sparks.
  3. Environment ControlKeep instrument room/box humidity 40%–55% to avoid condensation; clean graphite dust regularly.
  4. Explosion-Proof ComplianceAll instruments in grinding zones must be Ex d IIC T4 ATEX-certified; keep grounding resistance ≤4Ω.

1. Pressure Gauges & Pressure Transmitters Inspection & Maintenance

Covers: ordinary pressure gauges, digital pressure transmitters, differential pressure (DP) meters for mill air pressure, bag filter DP, system negative pressure.

1.1 Daily Visual Inspection (Shiftly, No Shutdown)

Inspection Item Standard Requirement Abnormal Judgment
Appearance & Glass No crack, no fogging, no graphite dust covering Blurred reading, glass broken
Pointer Status Pointer stable, no jitter; zero-position accurate Jitter violently, stuck, zero drift
Pressure Tube/Connector No air leakage, no graphite clogging Air bubble (soapy water test), pressure fluctuation
Reading Consistency Consistent with DCS/PLC display Deviation >5% of full scale
Bag Filter DP Gauge Normal: 800–1500 Pa >1800 Pa (clogged) or <500 Pa (bag broken/leakage)

1.2 Routine Maintenance (Weekly)

  1. Dust CleaningUse a soft brush + explosion-proof vacuum to wipe gauge surface, junction box, and pressure pipe; no high-pressure air blowing (avoids dust spreading).
  2. Seal CheckApply soapy water to pipe joints; tighten loose threads, replace damaged gaskets.
  3. Zero Calibration (On-Site)Vent the gauge to atmospheric pressure; adjust zero screw if pointer deviates.
  4. DP Meter PurgeBlow the pressure tapping port with dry nitrogen (0.2–0.3 MPa) to clear graphite fine powder clogging.

1.3 Periodic Calibration & Overhaul (Mandatory Metrology)

Instrument Type Calibration Cycle Calibration Standard Disposal Standard
Mechanical Pressure Gauge 6 months Dead-weight tester Precision ≤±1.6% FS
Digital Pressure Transmitter 12 months Precision pressure calibrator Precision ≤±0.5% FS
Differential Pressure Meter (Baghouse/Mill) 3 months Micro-pressure calibrator Deviation ≤±50 Pa

Overhaul Steps:

  1. Dismantle → clean internal graphite dust with dry cloth
  2. Replace damaged spring tube/sealing ring
  3. Calibrate zero & full range
  4. Seal and affix metrology qualification label

1.4 Common Faults & Fixes

Fault Cause Solution
Pointer stuck / no response Graphite dust clogging in pressure tube Purge with dry nitrogen; replace clogged capillary
Severe pointer jitter Pipeline vibration, air pressure instability Install damping valve; fix gauge firmly
Zero drift / reading inaccurate Spring fatigue, temperature influence Recalibrate or replace gauge
Air leakage at connector Thread wear, gasket aging Replace connector/gasket; apply thread sealant

2. Thermocouples & Temperature Sensors Inspection & Maintenance

Mainly K-type thermocouples (mill inlet/outlet, dryer, purification kiln, bearing temperature) and armored temperature sensors; graphite mills focus on anti-dust, anti-wear, and anti-condensation.

2.1 Daily Visual Inspection (Shiftly)

Inspection Item Standard Abnormal
Thermocouple Probe No bending, no graphite buildup, protective sleeve intact Sleeve worn/ broken, probe covered by thick graphite
Junction Box Sealed tight, no dust/moisture ingress Dust accumulation, water marks, loose terminals
Temperature Reading Stable, matches DCS; no sudden jump/drop Temp jumps >20°C, fixed value, no change
Cable & Insulation No damage, insulation good Cracked cable, short circuit

2.2 Weekly Maintenance

  1. Surface CleaningWipe the thermocouple protective sleeve with dry cloth; remove caked graphite powder (soft scraper only).
  2. Junction Box ServiceOpen the explosion-proof box → clean dust with dry brush → tighten wiring terminals → re-seal with gasket.
  3. Insertion Depth CheckEnsure probe insertion depth 100–150mm into air duct/mill wall (not too shallow, no contact with liner).
  4. Anti-Condensation TreatmentApply sealant to cable entry; install small heating pad in junction box for winter.

2.3 Periodic Calibration & Replacement

Sensor Type Cycle Calibration Method Replacement Standard
K-type Thermocouple 12 months Dry block calibrator (compare with standard temp) Deviation >±3°C
Armored Temperature Sensor 18 months Multi-point calibration (100°C/300°C/500°C) Protective sleeve worn through
Bearing PT100 6 months Precision resistance calibrator Resistance value abnormal

Calibration Key Points:

  • Calibrate at actual working temperature range (graphite grinding: 20–300°C; purification: up to 1200°C)
  • After calibration, fix the probe position to avoid displacement

2.4 Common Faults & Fixes

Fault Cause Solution
Temperature reading too low Probe loose, poor contact, sleeve covered by graphite Reinsert probe; clean sleeve; tighten terminals
Reading jumps randomly Loose wiring, short circuit, damaged insulation Rewire; replace cable; seal junction box
No temperature change Thermocouple broken, open circuit Replace thermocouple core
Reading drifts high Protective sleeve worn, probe in direct heat Replace sleeve; reposition probe

3. General Instrument Installation & Long-Term Protection (Graphite-Specific)

  1. Pressure Tapping Port DesignUse inclined upward tapping (45°) to prevent graphite powder deposition; install filter plug at the port.
  2. Thermocouple Protective SleeveUse stainless steel / ceramic sleeve for grinding zones; avoid direct wear by graphite particles.
  3. Sealing & DustproofAll instrument junction boxes use IP65/IP67 waterproof & dustproof grade; add silicone sealant for gaps.
  4. GroundingAll instruments, pipes, and junction boxes must be reliably grounded to eliminate static electricity.
  5. Spare Parts PreparationStock spare pressure gauges, thermocouples, DP sensors, sealing gaskets, and terminal blocks.

4. Complete Maintenance Cycle Summary (Easy for Workshop Posting)

Frequency Tasks for Pressure Instruments Tasks for Temperature Instruments
Per Shift Check reading, pointer, leakage Check temp stability, probe appearance
Weekly Clean dust, purge tapping port, zero check Clean probe, tighten wiring, seal box
Quarterly DP meter calibration, pipe inspection Thermocouple function test
Half-Year Pressure gauge full calibration Sleeve wear inspection
Yearly Transmitter calibration, replacement Thermocouple calibration & replacement

5. Key Notes for Graphite Processing

  • Never use water to clean instruments → causes graphite caking and short circuit.
  • Always use dry nitrogen for purging pressure pipes (no oil/water in air).
  • Replace instruments immediately if they fail calibration to avoid wrong grinding pressure/temperature control.
  • Record all calibration data in the instrument maintenance log for traceability.
About Us:

With over 20 years of dedicated expertise in ultrafine grinding technology, we deliver high-performance machinery that matches the precision and reliability of leading German and Japanese brands—at only 1/3 of their cost.

Beyond Equipment, We Deliver Total Confidence:

We provide Free Material Testing to ensure precise equipment selection, followed by professional on-site installation and comprehensive training. Our 24/7 technical support team ensures your production line remains efficient and worry-free.

Schedule Material Trial & Get a Customized Solution from Us
How to perform a risk assessment before non-routine maintenance
Non-routine maintenance refers to unplanned/special work: mill disassembly, classifier wheel removal, bag filter overhaul, pressure...
How to Deal with a Sudden Loss of Grinding Pressure
Sudden loss of grinding pressure is a critical issue that can immediately reduce product fineness,...
How to Check the Alignment of Couplings Between Motor and Mill
Proper coupling alignment between motor and mill is critical to prevent excessive vibration, premature bearing...